Routine Metal Expansion Joints
Routine (Tanesh) welded and flanged expansion joint: 10 and 16 bar, 200 °C design temperature, sizes ½ to 24 inch (catalog table), for HVAC, engine exhaust and heat exchangers.
Interactive maps and models
…
Applications & industries
Expansion Joint Calculator
Compute equivalent displacements and reaction forces in real time.
Input parameters
Joint type
Equivalent displacement per convolution
Live resultsAxial (ex)
1.000mm
Lateral (ey)
1.000mm
Angular (eθ)
0.349mm
Total displacement
2.349mm
Within allowable limit
Reaction forces from displacement
Axial force (FBX)
15.00kg
Lateral force (FBY)
5.00kg
Angular moment (Mθ)
261.80kg·mm
- ex
Equivalent axial displacement
Singleex=X / n
Doubleex=X / (2n)
- ey
Equivalent lateral deflection
Singleey=(3 × Dm × Y) / (L × n)
Doubleey=(3 × Dm × Y) / [(L + ℓ(ℓ/L + 1)) × 2n]
- eθ
Equivalent angular displacement
Alleθ=(Dm × π × θ) / (360 × n)
- Σe
Allowable criterion
Limiteallow ≥ ex + ey + eθ
- F
Forces and moment
AxialFBX=fB × ex
LateralFBY=(fB × Dm × ey) / (2L)
MomentMθ=(fB × Dm × eθ) / 4
Expansion Joint Order Questionnaire
Complete each step in order. Fields marked with * are required.


info@iivco.org